Investigation of the number of particles in an operating room at different ambient temperatures and inlet velocities


Ufat H., Kaynakli Ö., Yamankaradeniz N., Yamankaradeniz R.

INTERNATIONAL JOURNAL OF VENTILATION, cilt.17, sa.3, ss.209-223, 2018 (SCI-Expanded) identifier identifier

  • Yayın Türü: Makale / Tam Makale
  • Cilt numarası: 17 Sayı: 3
  • Basım Tarihi: 2018
  • Doi Numarası: 10.1080/14733315.2017.1392107
  • Dergi Adı: INTERNATIONAL JOURNAL OF VENTILATION
  • Derginin Tarandığı İndeksler: Science Citation Index Expanded (SCI-EXPANDED), Scopus
  • Sayfa Sayıları: ss.209-223
  • Anahtar Kelimeler: Indoor air quality, operating room air conditioning, particle counting, operating room, LAMINAR AIR-FLOW, VENTILATION PERFORMANCE, INDOOR ENVIRONMENT, AIRBORNE INFECTION, THERMAL COMFORT, QUALITY, THEATER, CONTAMINATION, SYSTEM, STAFF
  • Bursa Uludağ Üniversitesi Adresli: Evet

Özet

This study presents some field measurements in an operating room of air velocity, ambient temperature and particle counts on the operating table. Moreover, computational fluid Dynamics analyses of the operating room were performed and compared with the measurements. Measurements were taken under the preferred operating conditions by surgical staff (at 19 degrees C) and then at different ambient temperatures (from 20 to 22 degrees C, varying by one-degree increments) and average inlet air velocities (V-j) (0.1 and 0.2 m/s). The preferred one by surgical staff is 0.1 m/s and the maximum that can be reached is 0.2 m/s, with the current system. The results show that the particle count decreased at V-j of 0.2 m/s and low temperatures.